AC Power Sensor Kit

Manage. Monitor. Control.
Three-Phase Mains Voltage Monitoring

AC Power Sensor Kit

Catch a lost phase or a sagging feed before it takes equipment down. The AC Power Sensor Kit turns each phase of your three-phase supply into a clean analog signal your GPX reads, trends and alarms on.

The kit uses a CR Magnetics CR4870 average RMS AC voltage transducer for three-phase, four-wire (wye) services up to 500 V. It produces three isolated 0–5 VDC outputs, one per phase, that wire straight into three GPX analog inputs. No extra interface hardware is needed.

Key Features
  • One output per phase. See each phase on its own channel, so a single dropped phase is obvious.
  • Wires straight to GPX. 0–5 VDC outputs match the analog inputs on the GPX-32, GPX-32 Pro and GPX-8 Pro.
  • Isolated and safe. Outputs are isolated from the line inputs, with 2,500 VDC insulation.
  • Easy to mount. 35 mm DIN rail or panel mount, with the connection diagram printed on the case.
What's Included
  • CR Magnetics CR4870-500 AC voltage transducer, 3-phase 4-wire (wye), 0–500 V input
  • Wall-mount power supply

A 0–250 V version (CR4870-250) is available for lower-voltage services; contact us to order it.

Compatibility: GPX-32, GPX-32 Pro and GPX-8 Pro. Uses three analog inputs.

Specifications

AC Power Sensor Kit

How It Connects

AC Power Sensor Kit

Connect L1, L2, L3 and neutral from the service to the transducer inputs; this side should be installed by a qualified electrician. Wire the three 0–5 VDC outputs to three analog inputs on the GPX. On a GPX-32 or GPX-32 Pro, set that input bank to the ±5 V range. On a GPX-8 Pro, set each of the three inputs to ±5 V in SLS WebControls. Scale each channel to read 0–500 V, then set alarm limits for high, low and lost phase.

Downloads

Order & Documentation

Buy the AC Power Sensor Kit — $267.00
CR Magnetics CR4870 Specifications
Need the 250 V version? +1.888.418.3646